Path:
… > PARA > STEP V1
Setting values
… > PARA > STEP V2
Display
Name
Range
Factory setting
S1-ON
[Step 1] ON
0…100 %
17 %
S1-OFF
[Step 1] OFF
0…100 %
1 %
S2-ON
[Step 2] ON
0…100 %
33 %
S2-OFF
[Step 2] OFF
0…100 %
17 %
S3-ON
[Step 3] ON
0…100 %
50 %
S3-OFF
[Step 3] OFF
0…100 %
33 %
S4-ON
[Step 4] ON
0…100 %
67 %
S4-OFF
[Step 4] OFF
0…100 %
50 %
S5-ON
[Step 5] ON
0…100 %
83 %
S5-OFF
[Step 5] OFF
0…100 %
67 %
S6-ON
[Step 6] ON
0…100 %
100 %
S6-OFF
[Step 6] OFF
0…100 %
83 %
OFFTIME Locking time
00.00…10.00 m.s
00.00 m.s
MIN POS
Positioning signal min
0…100 %
0 %
MAX POS Positioning signal max
0…100 %
100 %
INVERS Inversion
NO,
YES
NO
Note
STEP V1 has a maximum of 2 steps.
Therefore, the setting values for S3-ON to S6-OFF are not shown.
Path:
INFO
Display values
Display
Name
Comments
STEP V1
Variable step switch 1
0…100 %
STEP x
Variable step switch 1, step x
ON, OFF
STEP V2
Variable step switch 2
0…100 %
STEP x
Variable step switch 2, step x
ON, OFF
Path:
… > COMMIS > TEST
Wiring test
Display
Name
Positions
STEP V1
Variable step switch 1
---, 0…100 %
STEP x
Variable step switch 1, step x
ON, OFF
STEP V2
Variable step switch 2
---, 0…100 %
STEP x
Variable step switch 2, step x
ON, OFF
78 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Aggregates
29.08.2008