Operating principle
(cont’d)
Additionally, you can enter a common locking time for the digital outputs. This
ensures that a stage that has just switched off remains off for at least the set period
of time.
Locking time
(OFFTIME)
You cannot enter an overrun time for the step switches, since there are no open-
loop control functions in the Synco 200 product range.
No overrun time in the
step switch
If the variable step switch is controlling an electric air heater battery, you must
solve the fan overrun time using external means.
Note
8.4.3
External preselection (IN X)
You can configure an analog input as a preselection for the step switch. The
controller performs a maximum selection together with the internal signals.
Maximum selection in
case of several
preselections
For example, you can use this feature to implement the following function:
External control. The RLU236 provides the step switch function only.
The external signal is considered only if the controloler is in Comfort or Economy
mode!
Note
8.4.4
Output inversion (INVERS)
You can invert the analog output. Meaning:
Definition and behavior
INVERS = NO:
0…100% load = 0…100% output
INVERS = YES:
0…100% load = 100…0% output
If the controller with a variable step switch is switched off during operation (input
D1 = Protection), the output signal behaves as follows:
INVERS = NO:
0% output
INVERS = YES:
100% output
76 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Aggregates
29.08.2008