8.1.6
Settings
Path:
… > COMMIS > CONF > PUMP 1
Configuration
… > COMMIS > CONF > PUMP 2
… > COMMIS > CONF > PUMP 3
Display
Name
Range / comments
PUMP x
Output
Output of pump x (1, 2, 3) to a relay;
adjustable values: ---, Q1, Q2, … (free
outputs only)
Path:
… > PARA > PUMP 1
Setting values
… > PARA > PUMP 2
… > PARA > PUMP 3
Display
Name
Range
Factory setting
Y ON
Load-dependent ON
0…100 %
5 %
OFF-Y
Load-dependent OFF
0…100 %
0 %
ON-OUTS Outside
temp-dependent
ON
−
50…
+
250 °C
−
50 °C
DLY OFF
Switch-off delay
00.00…60.00 m.s
00.00
KICK Kick
period
0…200h
0
Path:
INFO
Display values
Display
Name
Comments
PUMP 1
Pump 1
Indication of current state: Off, On…
PUMP 2
Pump 2
Indication of current state: Off, On…
PUMP 3
Pump 3
Indication of current state: Off, On…
Path:
… > COMMIS > TEST
Wiring test
Display Name
Positions
PUMP 1
Pump 1
Off, On…
PUMP 2
Pump 2
Off, On…
PUMP 3
Pump 3
Off, On…
57 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Aggregates
29.08.2008