3.2.2
Access levels
RLU2… universal controllers have 3 access levels. They are:
3 access levels
•
User level
•
Service level
•
Password level
Each data point is assigned one of these access levels.
The following table contains the 3 access levels and their purpose, access and
symbols:
Access
Level
Access
Symbol
User level
(for plant
operator)
The user level can be accessed any time.
Users can modify all data points that are visible
/ adjustable at this level.
None
Service level
(for maintenance)
1.
Simultaneously press the
OK
and
ESC
buttons.
2.
Press the "
+
" / "
–
" buttons to select
service level
SERV
.
3. Press
the
OK
button to confirm your
choice.
SERVICE
Password level
(for
commissioning)
1.
Simultaneously press the
OK
and
ESC
buttons.
2.
Press the "
+
" / "
–
" buttons to select
password level
PASS
.
3. Press
the
OK
button to confirm your
choice.
4. When
PASSWRD
is displayed, press the "
+
" button to select figure
2
.
5. Press
the
OK
button to confirm your
choice.
PASS
The 3 access levels share the following properties:
Common properties
•
The access level determines which individual menus and operating lines are
activated
•
A higher access level also shows the menus and operating lines for the lower
access levels
•
The levels use a shared menu as a basis
•
The password level contains the entire menu
•
After a timeout of 30 minutes (period of time during which the controller is not
operated), the controller switches to the user level