10.3.5 2-stage frost protection on the water side (NI)
This picture shows an application with 2-stage, water-side frost protection:
Application example
AI
31
01
S
2
4
X1
x Y
SI
G
N
AL
Y
LABEL
FRST
Notes on engineering
Observe the following points with regard to sensor placement and the heating
circuit pump:
•
Reliable frost protection depends on correct sensor placement!
Position the sensor in or on the water-side outlet of the air heating coil within the
air duct
•
As an additional protection function, the heating circuit pump must switch on
automatically at outside temperatures below 5 °C (setting value "On according to
outside temperature", refer to chapter 8 “Pump (PUMP x)”
If the temperature falls below the set starting point (= limit value + 2 K + P-band),
the heating sequences are steplessly opened and the cooling sequences are
steplessly closed. The purpose is to prevent the temperature from falling below the
"frost hazard" limit value (SET-ON).
Temperature drops
below starting point
If the temperature still drops below the above limit value, the following reactions are
triggered:
Actions if temperature
drops below limit value
•
The fan release relay is deenergized (no release of fan)
•
The control loop configured with the air heating coil at risk from frost switches off
all cooling sequences and opens all heating sequences to 100% It also switches
on the air heating coil pump.
=> Important: Step switches are also switched on in the process!
•
If 2 controllers are configured in the RLU2…, the second (other) control loop is
switched off as well
•
The outside air dampers are closed
142 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Frost protection (FROST)
29.08.2008