9.9.3
Troubleshooting
If there is no outside temperature sensor signal, the controller does not shift the
setpoint.
OT sensor signal
available?
9.9.4
Settings
Path:
… > PARA > CTLOOP 1
Setting values
Display
Name
Range
Factory
setting
SUM-D Summer
compensation
delta
0…+50 K
0 K
SUM-END Summer
compensation
end
SUM-STT…50 °C
30 °C
SUM-STT Summer
compensation
start
WIN-STT…SUM-END 20
°C
WIN-STT Winter
compensation
start WIN-END...SUM-STT 0
°C
WIN-END Winter
compensation
end
−
50 °C…WIN-STT
−
10 °C
WIN-D Winter
compensation
delta
−
50…+50 K
0 K
130 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Controller (CTLOOP x)
29.08.2008