7.2.8
Settings
Path:
… > COMMIS > CONF > X1…X5
Configuration
Display
Name
Range / comments
LABEL Input
identifier
Assignment of ROOM, OUTS, SAT,
TEMP, %, 0.0, 0000
SIGNALY
Measured value signal output Output of passive temperature
sensor as active signal
Path:
… > PARA > X1…X5
Setting values
Display
Name
Range
Factory setting
TYPE
Type
NI, 2XNI, T1, PT, 0-10
NI
MIN VAL
Value low
−
50…
+
500 (with analog
signals only)
-50
MAX VAL Value high
−
50…
+
500 (with analog
signals only)
250
CORR Correction
−
3.0…
+
3.0 (with °C only)
0 K
Path:
INFO
Display values
Display
Name
Comments
X1
X1
Display of current measured value at terminal X1
… …
…
X5
X5
Display of current measured value at terminal X5
Path:
… > COMMIS > TEST
Wiring test
Display
Name
Positions
X1
X1
Display of current measured value at terminal X1,
non-adjustable
… …
…
X5
X5
Display of current measured value at terminal X5,
non-adjustable
Display
Name
Effect
Xx --- / ooo Sensor error
Xx…
Non-urgent message; plant not stopped.
However, if sensor is used for the main controlled
variable: Plant stopped
Fault status messages
43 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Inputs
29.08.2008