9.2.6
Implementation: Room temperature control
9.2.6.1
Activation and setpoints
Room temperature control can only be activated for controller 1, basic type A. To
activate room temperature control, assign input identifier ROOM to the room
temperature.
Activation
9.2.6.2
Operating principle
PID control is used to maintain the room temperature at the adjusted setpoint.
PID control
9.2.6.3
Troubleshooting
When you leave the commissioning menu, the universal controller checks whether
a room temperature sensor is connected.
Room temperature
sensor present?
•
If, at that time, a room temperature value is available, but is missing later, a
sensor error message is delivered and presented on the display:
"Xx ---" => sensor missing or
"Xx ooo" => short-circuit
•
If, at that time, there is no room temperature value (main controlled variable in
this case), the plant will be shut down (MAINALM):
9.2.6.4
Settings
Path:
… > COMMIS > CONF > CTLOOP 1
Configuration
Display
Name
Setting
STRATGY Control
strategy
---
97 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Controller (CTLOOP x)
29.08.2008