162 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Appendix
29.08.2008
Aggregates
(cont
’d)
STEP Vx
(variable
step switch)
Configuration
Functions
y1 y2
x
Q Q Q Q Q Q
Y
IN X
S
T
E
P
1
S
T
E
P
2
S
T
E
P
3
S
T
E
P
4
S
T
E
P
5
S
T
E
P
6
AO
STEP V2
•
Step 1 to … (STEP x)
•
Modulating output (AO)
•
External signal (IN X)
For controlling a multistage aggregate.
•
A switch-on and switch-off point can be assigned to each step
according to the load signal from the sequence controller (from up to
2 sequences with maximum selection) The switching points can
overlap and can be inverted (ON < OFF)
•
External load signal can be applied
•
Configurable modulating output. Same function as modulating outputs
AO x
•
Locking time (restart delay) is adjustable (time applies to all steps)
STEP LIN
(linear step
switch)
Configuration
Functions
y1 y2
x
Q Q Q Q Q Q
Y
IN X
S
T
E
P
2
S
T
E
P
3
S
T
E
P
4
S
T
E
P
5
S
T
E
P
6
AO
S
T
E
P
1
STEP LIN
•
Step 1 to … (STEP x)
•
Modulating output (AO)
•
“External preselection” input (IN
X)
For controlling a multistage aggregate.
•
Linear distribution of the steps over the load signal range according to
the number of outputs assigned
•
External load signal can be applied
•
Modulating output can be configured, same function as modulating
outputs AO x
•
Locking time (restart delay) and startup delay time are adjustable
(time applies to all steps)
•
Weekly priority changeover of the steps
STEB BIN
(binary
step switch)
Configuration
Functions
y1 y2
x
Q Q Q Q
Y
IN X
S
T
E
P
2
S
T
E
P
3
S
T
E
P
4
S
T
E
P
1
AO
STEP BIN
•
Step 1 to … (STEP x)
•
Modulating output (AO)
•
“External preselection” input (IN
X)
For controlling a multistage aggregate.
•
Binary distribution of the steps over the load signal range according to
the number of outputs assigned
•
External load signal can be applied
•
Modulating output can be configured, same function as modulating
outputs AO x
•
Locking time (restart delay) is adjustable (time applies to all steps)
3P
(3-position)
Configuration
Functions
y1 y2
IN
X
x
Q1
Q2
OP
EN
CL
OSE
3 P
3 POINT
•
3-position
output
(3-POINT)
•
“External preselection” input (IN
X)
For controlling a 3-position actuator.
•
End stop synchronization
•
External load signal can be applied
•
Actuator running time adjustable