7.5.5
Troubleshooting
When you leave the commissioning menu, the universal controller checks whether
the setpoint adjuster is connected.
Connection errors
•
If, at that time, the setpoint adjuster is connected, but is missing later during
operation, or if there is a short-circuit in the cable, a sensor error message is
delivered and presented on the display:
–
"Xx ---"
=> setpoint adjuster missing
–
"Xx ooo"
=> short-circuit
•
If, at that time, there is no signal from the setpoint adjuster at the time, the
controller operates without the relative setpoint shift
If you have activated more than one input as the relative remote setpoint adjuster,
the controller only accepts the first input.
Configuration errors
7.5.6
Settings
Path:
… > COMMIS > CONF > X1…X5
Configuration
Display
Name
Range / comments
LABEL Input
identifier REL
Path:
INFO
Display values
Display
Name
Comments
Xx
Xx
Indication of present relative remote setpoint
adjuster value at terminal Xx
Path:
… > COMMIS > TEST
Wiring test
Display
Name
Positions
Xx
Xx
Indication of present relative remote setpoint
adjuster value at terminal Xx, non-adjustable
Display
Name
Effect
Xx --- / ooo Sensor error X…
Non-urgent message; plant not stopped
Fault status messages