8.3.3
Heat recovery changeover (TYPE)
To produce the changeover between HR equipment (wheel, glycol) and mixing
dampers, you can invert the output signal using TYPE.
Output inversion
You have to make the following settings in normal operation to achieve the
customary control response:
Settings
•
HR equipment:
\_
TYPE = ERC
0…100% load = 0…100% output
•
Mixing damper:
/_
TYPE = DMP
0…100% load = 100…0% output
This response applies if the HR equipment (HREC) is connected to the SEQ1 Y
heating sequence of the CTLOOP controller.
Note
If the controller with a HR equipment / mixing damper output is switched off during
operation (input D1 = Protection ), the output signal behaves as follows:
Output signal behavior
•
TYPE = ERC:
0% (i.e. DC 0 V)
•
TYPE = DMP:
0% (i.e. DC 0 V)
8.3.4
Limitations (MIN POS, MAX POS)
You can impose upper and lower limits on the modulating output.
Diagram
In that case, the 0…100% output signal corresponds to:
Minimum positioning signal (MIN POS)…maximum positioning signal (MAX POS).
0 %
100 %
0 %
0 V
100 %
10 V
MAX POS
Y
Qs
31
01
D
05
MIN POS
Qs = load demand from the sequence controller
You can implement a minimum air damper position using the minimum positioning
signal (MIN POS).
Application example
The controller does not give consideration to MIN POS and MAX POS in Protection
mode.
Note
63 / 174