Anti-icing protection for the HR unit,
acting on sequence 1 (Y6), closing.
Application example,
HR
The temperature at limit sensor B21 must, for example, be at least 0 °C
(SEQ SET), otherwise throughput will be steplessly limited by Y6.
Basic diagram
Function diagram
M
M6
Y6
T
T
M
Y3
M3
31
01
S
35
B21
Yctl
1
0
TSu
31
01
D
04
M3
Y6
Y3
M6
SpTSuH
In a boiler with risk of corrosion, the return temperature (water inlet temperature at
B7) is prevented from falling below a certain level, acting on sequence 1 (Y3):
Application example,
boiler
M
T
T
N.X1
B1
Y3
N.Q1
N.Q2
N.X2
B7
31
0
1S
3
6
If the controlled variable exceeds the limit setpoint (SEQ SET), the limit function
with PI control (SEQ XP, SEQ TN) overrides the normal control function to maintain
the limit setpoint.
Maximum limitation
Maximum limitation causes the sequence to close.
Maximum limitation of the return temperature (TRL), acting on sequence 1 / valve
M:
Application example, air
heater
Basic diagram
Function diagram
T
B1
T
M
TRL
31
01
S
37
M6
Yctl
1
0
TSu
31
01
D
06
SpTSuH
M6
SEQ1 Y
125 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Controller (CTLOOP x)
29.08.2008