7.6
Outside temperature (OUTS)
7.6.1
Activation and functionality
You can activate the function by setting identifier
OUTS
(outside temperature) at
the respective input.
Activating the function
OUTS (outside temperature) is a special identifier, because it creates a large
number of internal connections.
The other properties, such as measuring range, troubleshooting, etc., are
described in chapter 0 "Analog inputs".
Additional functionality
7.6.2
Settings
Path:
… > COMMIS > CONF > X1…X5
Configuration
Display
Name
Range / comments
LABEL Input
identifier
OUTS
Path:
… > PARA > X1
Setting values
… > PARA > X5
Display
Name
Range
Factory setting
TYPE
Type
NI, 2XNI, T1, PT, 0-10
NI
MIN VAL
Value low
−
50…
+
500 -50
MAX VAL Value high
−
50…
+
500 250
CORR Correction
−
3.0…
+
3.0 0
K
Path:
INFO
Display values
Display
Name
Comments
OUTS Outside
temperature
Path:
… > COMMIS > TEST
Wiring test
Display
Name
Positions
OUTS
Outside temperature
Indication of outside temperature (at
terminal Xx and as special data point
OUTS), non-adjustable
Display
Name
Effect
Xx --- / ooo Sensor error X…
Non-urgent message; plant not stopped
Fault status messages
51 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Inputs
29.08.2008