9.3.4
Setpoints
The following applies to controller 2, basic type A, and controllers 1+2, basic type
U:
Preselections
•
You can assign individual setpoints for the Comfort and Economy modes.
•
We distinguish between the following setpoints:
–
SET MIN
lower setpoint "Heating" (sequence 1+2)
–
SET MAX
upper setpoint "Cooling" (sequence 4+5)
These functions can have an influence on the setpoints:
Influences on the
setpoints
•
Universal setpoint shift
•
Remote setpoint, absolute
9.3.5
Troubleshooting
Incorrect configuration has the following effect:
Effect of incorrect
configuration
Configuration point
Setting
Effect
Main controlled variable (MAIN)
dDifferential input (DIFF)
--- (not relevant)
Controller inactive
Main controlled variable (MAIN)
Differential input (DIFF)
Xx (analog)
Xx (not same unit as
main controlled variable)
Control to absolute
value, no differential
control
When you leave the commissioning menu, the universal controller checks whether
a main sensor is connected.
Main sensor present?
•
If, at that time, the main sensor is connected, but is missing later, or if there is a
short-circuit in the cable, a sensor error message is delivered and shown on the
display:
–
"Xx ---"
=> main sensor missing
–
"Xx ooo"
=> short-circuit
•
If, at that time, there is no main sensor (main controlled variable in this case),
the plant will be shut down (MAINALM)
9.3.6
Configuration
Path:
… > COMMIS > CONF > CTLOOP 1
Controller 2, basic type
A; controllers 1+2,
basic type U
Path:
… > COMMIS > CONF > CTLOOP 2
Display
Name
Adjustable values / comments
MAIN
Main controlled variable Activation of main controlled variable.
Adjustable values:
---, X1, X2, … (analog values only)
DIFF
Differential input
Activation of difference control
Adjustable values:
---, X1, X2, … (analog values only)
106 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Controller (CTLOOP x)
29.08.2008