Page 54
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmmm
m
Alarms
In Bounds/ Out of Bounds Range [6 relay model]
Use the bounded range alarms to detect when the level is inside or outside of the range.
By using a bounded range alarm, you can effectively put two level alarms (high and low)
on one relay.
Setting an Out of Bounds Alarm
Results:
•
Trips alarm above 1.35 m and below 0.25m
•
Resets alarm below 1.25 m and above 0.35m
Setting an In Bounds Alarm
Results:
•
Trips alarm below 1.25 m and above 0.35 m
•
Resets alarm above 1.35 m and below 0.25 m
Cable Fault
Activates an alarm if transducer cable circuit enters a shorted or opened state.
Temperature [6 relay model]
Use the temperature alarm to activate an alarm when the temperature reaches the ON
setpoint (P112). This alarm uses the same setpoint parameters as the level alarms (P112
and P113).
Parameter
Index
Value
P111
5
3
P112
5
1.3
P113
5
0.3
P116
5
0.05
Parameter
Index
Value
P111
5
2
P112
5
1.3
P113
5
0.3
P116
5
0.05
Parameter
Index
Value
Description
P111
5
7
Alarm on transducer cable fault
P110
5
1
Alarm on Transducer One
Содержание HydroRanger 200
Страница 1: ...Instruction Manual July 2009 200 hydroranger ...
Страница 232: ...Page 222 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Parameters Notes ...
Страница 264: ...Page 254 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Appendix H Software Rev Notes ...
Страница 278: ...Notes ...
Страница 279: ......