7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 161
mmm
mm
Pa
ra
m
e
te
rs
To display a record
Press
key to enter display auxiliary mode and then:
•
Press TRANSDUCER
to copy the current echo profile into the buffer for display
on Dolphin Plus
To delete a record
Press CLEAR
and then ENTER
to delete the echo profile record in the selected
address. The value returns to
- - - -
.
P331 Auto Record Enable
Use to enable/disable the Auto Profile Record function.
P332 Auto Record Transducer
Specifies the Transducer Point Number for which Auto Profile Records are saved.
Please note that Differential and Average operation is a feature of the HydroRanger 200
6 relay model.
HydroRanger 200 [6 relay model]
This feature is preset to Point Number 1. (Alteration is only required if
differential
or
average
Operation [P001 = 4 or 5] is selected.)
Primary Index
Global
Values
Range: 0 to 1
0
*
Off
1
On
Primary Index
Global
Values
Range: 0 to 2
0
Any transducer
1
*
Transducer One
2
Transducer Two
Altered By
•
P001 Operation = 4 or 5