Page 216
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Pa
ra
m
e
te
rs
P902 Watchdog
Press ENTER
to put the CPU into an infinite loop to test the watchdog timer.
On successful completion (10 seconds) the RUN mode is entered and the HydroRanger
200 is reset. Programming is kept and the unit responds as if there had been a power
failure.
P903 Display
Press ENTER
to activate the display test.
All LCD segments and symbols are temporarily displayed.
P904 Keypad
Press ENTER
, then press each keypad key in the following sequence:
As each key is pressed, the associated keypad number is displayed. On successful test
completion, PASS is displayed. FAIL is displayed if a key is pressed out of sequence or the
programmer keypad malfunctions.
P905 Transmit Pulse
Press ENTER
to supply repeated transmit pulses, at the frequency entered, to the
transducer and / or view the transducer operating frequency (automatically altered by
P004 Transducer) for the Point Number displayed.
P906 RS-232 Port
Press ENTER
to test the RS-232 port on the RJ-11.
An external device must be connected to the RS-232 port for this test. On successful
completion, PASS is displayed, otherwise it is FAIL.
Primary Index
Single Point Model
Dual Point Model
Global
Transducer
Values
Range: 42kH to 46KH (view only)
Altered By
•
P004 Transducer
P