Page 126
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Pa
ra
m
e
te
rs
Entering a Level Breakpoint
1.
Go to Parameter P054.
2.
For each index enter a breakpoint in measurement units.
3.
Ensure that each breakpoint corresponds to the same index for P055.
P055 Volume Breakpoints and Characterization
(Universal Volume Calculation) [6 relay model]
Each segment defined by the level breakpoints (P055) requires a volume so that the
HydroRanger 200 can make the level-to-volume calculations.
Typical volume calculations
Entering a Volume Breakpoint
1.
Go to Parameter P055.
2.
For each index enter a volume.
3.
Ensure that each volume corresponds to the same index for P054.
For more on
Volume Characterization
, go to page 50.
Display and Reading (P060 to P062)
These parameters are used to:
•
Change the number of decimal places displayed
•
Convert the Reading to alternate units
•
Reference measurements to other than Empty (P006) or Span (P007)
Primary Index
Level
Secondary Index
Breakpoint
Values
Range: 0.0 to 99999
Related
•
P054 Breakpoints Levels (Universal Volume Calculation)
Cone
Cylinder
V = (1/3)
π
r
2
h
V =
π
r
2
h