7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 223
m
mmmm
Append
ix A: Index T
ypes
Appendix A: Index Types
Index types
Name
Description
# of indexes
Global
This parameter applies to the entire unit
n/a
View only
This parameter can not be set, only viewed
n/a
Breakpoint
Indexed by breakpoint
Parameter depen-
dent
Dimension
Indexed by PMD dimension
up to 7
Discrete Input
Indexed by discrete input
2
Echo Profile
Indexed by stored echo profile
10
Level Point
1
1.
HydroRanger 200 (1 or 3 relay model): This model is only a single point
device, therefore the level point index is always 1.
HydroRanger 200 (6 relay model): The three level points are: transducer
1, transducer 2, and the calculated point which can be difference
(P001=4) or average (P001=5).
Level point typically has 1 index in Single Point Mode (standard), and 2
indexes in Dual Point Mode (optional). A third index is available in both
modes when Operation (P001) is set for DPD (P001=4) or DPA (P001=5).
Indexed by level point
1, 2 or 3
mA input
1
Indexed by mA input
1
mA output
1
Indexed by mA output
0 or 2
Comm. Port
Indexed by communications port
2
Relay
Indexed by relay
1, 3 or 6
Transducer
2
2.
HydroRanger 200 (6 relay model): The number of indexes available in
Single Point Mode (standard) is typically 1, but can be expanded to 2 if
Operation (P001) is set for DPD (P001=4) or DPA (P001=5).
In Dual Point Mode (optional), the number of available indexes is
always 2.
Indexed by transducer
1 or 2