The HydroRanger 200 was designed to make it easy for master devices to get useful
information via Modbus. This chart gives an overview of the different sections. A more
detailed explanation of each section follows below.
Word Order (R40,062)
This determines the format of unsigned, double-register integers (UINT32).
•
0 indicates that the most significant word (MSW) is given first
•
1 indicates that the least significant word (LSW) is given first
See
Unsigned Double Precision Integer (UINT32)
on page 105 for more information.
Map ID (R40,063)
This value identifies the register map used by the HydroRanger 200. See
P782 Parameter
Index Location
on page 94.
See also
Parameter Access (R43,998 – R46,999)
on page 100 for details.
Type
Description
Start
#R
1
1.
Maximum registers shown; fewer may be used depending on options installed.
Data Type
Read/
Write
Point
Data
Temperature (2)
41,030
2
–50 to 150
R
Totalizer for points 1
and 2 [6 relay
model]
41,040
4
UINT32
R/W
I/O
Discrete Inputs (2)
41,070
1
Bit Mapped
R
Relay Outputs (all
models)
41,080
1
Bit Mapped
R/W
mA Input (1)
[6 relay model]
41,090
1
0000 to
20,000
R
mA Output (2)
41,110
2
0000 to
20,000
R/W
Pump
Control
Pump on Setpoint
(all models)
41,420
6
0000 to
10,000
R/W
Pump off Setpoint
(all models)
41,430
6
0000 to
10,000
R/W
Pumped Volume (2)
[6 relay model]
41,440
4
UINT32
R
Pump Hours (all
models)
41,450
12
UINT32
R
Pump Starts (all
models)
41,470
6
0000 to
10,000
R
Parameter Access
43,998 to 46999
R/W
Note:
Additional information is available from our Web site at www.siemens.com/
processautomation