
Page 166
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Pa
ra
m
e
te
rs
The HydroRanger 200 is pre-programmed for common PMD flow calculations. If your
PMD is not listed, select the appropriate Universal Flow Calculation.
Associated parameters Max Head (P603), Max Flow (P604), and Min Head (P605) may be
scroll accessed. If Operation is not set for OCM (P001 = 6), this value is preset to 0. If
Operation is set for OCM, it is preset to 1.
P601 Flow Exponent [6 relay model]
The Exponent for the flow calculation formula.
Use this parameter if the Primary Measuring Device (P600) is set to 1 (exponential). It
creates an exponential curve with end points set by Max Head (P603) and Zero Head
(P604) and with the curve based on the specified exponent.
Use the exponent specified by the PMD manufacturer, if available, or the sample value
given below.
Related
•
P603 Maximum Head
•
P604 Maximum Flow
•
P605 Zero Head
•
P610 Head Breakpoints
•
P611 Breakpoint
Primary Index
Single Point Model
Dual
Global
Transducer
Values
Range: -999 to 9999
Preset: 1.55
Altered By
•
P600 Primary Measuring Device
Related
•
P603 Maximum Head
•
P604 Maximum Flow
•
P605 Zero Head
Max. Flow
(P604)
Zero Flow
Ze
ro
H
ead
Ma
x. Head (P
60
3)
If P601 = 1, the flow characteristic is a straight line
A Word on Exponents
The exponential equation is
Q = KH
P601
Where:
Q = flow
K = internal constant
H = head
Содержание HydroRanger 200
Страница 1: ...Instruction Manual July 2009 200 hydroranger ...
Страница 232: ...Page 222 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Parameters Notes ...
Страница 264: ...Page 254 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Appendix H Software Rev Notes ...
Страница 278: ...Notes ...
Страница 279: ......