P003 Maximum Process Speed
Determines level change reaction.
Use a setting just fast enough to keep up with your process. Slower settings provide
higher accuracy. Faster settings allow for more level fluctuations.
P004 Transducer
Specifies the Siemens Milltronics transducer connected to the unit.
Primary Index
Transducer
Values
1
Slow (0.1 m/min)
2
*
Medium (1 m/min)
3
Fast (10 m/min)
Alters
•
P070 Failsafe Timer
•
P700 Max Fill Rate
•
P701 Max Empty Rate
•
P702 Filling Indicator
•
P703 Emptying Indicator
•
P704 Rate Filter
•
P710 Fuzz Filter
•
P713 Echo Lock Window
•
P727 Scan Delay
•
P841 Long Shot Number
Related
•
Failsafe (P070 to P072)
•
P121 Pump by Rate
•
Rate (P700 to P708)
•
Measurement Verification (P710 to P713)
•
Transducer Scanning (P726 to P729)
•
P905 Transmit Pulse
Primary Index
Single Point Model
Dual Point Model
Global
Transducer
Values
0
*
No transducer attached (preset for Dual Point)
1
ST-25
2
ST-50
100
STH
101
XCT-8
102 *
XPS-10 (preset for Single Point Model)
103
XCT-12
104
XPS-15
112
XRS-5
250
mA input [6 relay model]
(chart cont’d next page)