Example:
The flush valve connects to Relay Four and the watched pump is on Relay One.
Relay Controlled by Communications
A relay can be controlled directly by a remote system through communications. No other
control schemes can then be used with a relay configured this way. Communications can
be used to force status of some control relays, such as pumps.
Settings:
Tracking Pump Usage
You can find out how much an individual pump has been used by viewing the pump
records parameters.
Parameter
Index
Value
Description
P170
G
1
Watch Relay One to count pump cycles.
P171
G
3
Open the flush valve for 3 cycles.
P172
G
10
Use the flush value every 10 cycles.
P173
G
120
Open the flush valve for 120 seconds.
Parameter
Index
Value
Description
P111
5
65
Sets Relay Five to communications control.
Information Available
Parameter Access
Current RUN time
P309
Total pump hours
P310
Total pump starts
P311
Total pump RUN on occurrences
P312 [6 relay model ONLY]