HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Pa
ra
m
e
te
rs
If necessary, enter the Parameter Number to default in the Auxiliary Reading display. That
value will show in the auxiliary reading area by default. Other values are available but will
reset to the parameter defined here.
P731 Auxiliary Reading Key
Enter the Parameter Number whose value is to be displayed in the Auxiliary Reading field
is pressed in the RUN mode. See the
Hand Programmer
section on page 26 for RUN
mode auxiliary readings.
P732 Display Delay
Adjusts the Point Number display scroll speed.
Use this feature to adjust the delay before the display advances to the next Point Number.
Display scrolling is independent from transducer scanning.
P733 Scroll Access
Use this feature to select the parameter scroll access option desired.
Press READING
and
to tag / untag any accessed parameter.
is displayed to
indicate the parameter accessed is tagged.
Primary Index
Global
Values
Range: 000 to 999
Preset: Material Reading, P921
Primary Index
Global
Values
Range: 0.5 to 10
Preset: 1.5 seconds
Related
•
P001 Operation
•
P737 Primary Reading
Primary Index
Global
Values
0
Off
to scroll to all parameters (P001 to P999)
1
* Smart
for Quick Start, altered, and tagged parameters
2
Tagged
to scroll to operator tagged parameters only
Note:
Quick Start parameters (P001 – P007) and those changed from factory
default settings cannot be untagged.