7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 169
mmm
mm
Pa
ra
m
e
te
rs
Example
P605 Zero Head [6 relay model]
The distance above Empty (P006) in Units (P005) representing zero head (and zero flow).
This feature can be used for most weirs and some flumes (e.g. Palmer Bowlus) where the
zero reference is at a higher elevation than the channel bottom.
Conditions
Enter
•
Flowrate display: millions of gallons/day,
•
Maximum flowrate is 376,500,000 gallons/
day
•
376.5 for Maximum Flow (P604)
•
and 4 for Time Units (P606).
Primary Index
Single Point Model
Dual Point Model
Global
Transducer
Values
Range: -999 to 9999
Preset: 0.000
Altered By
•
P005 Units
•
P007 Span
Related
•
P006 Empty
•
P801 Range Extension
•
P926 Head Measurement
Zero Head (P605)
Empty (P006)
Transducer
Material level at zero flow
PMD base