P701 Max Empty Rate
Adjusts the HydroRanger 200 response to decreases in the actual material level (or
advance to a lower Failsafe Material Level, P071).
Enter a value slightly greater than the maximum vessel emptying rate. This value, in Units
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process
Speed (P003) is altered.
P702 Filling Indicator
The fill rate required to activate the LCD Filling indicator ( ).
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of
the Max Fill Rate (P700).
Primary Index
Single Point Model
Dual Point Model
Global
Transducer
Values
Range: 0.000 to 99.00 m (or equivalent depending on units)
Altered by
•
P003 Maximum Process Speed
Related
•
P005 Units
•
P007 Span
•
P071 Failsafe Material Level
P003 Value
Meters / Minute
1
0.1
2
1
3
10
Primary Index
Single Point Model
Dual Point Model
Global
Transducer
Values
Range: 0.000 to 99.00 m (or equivalent depending on units)
Altered by
•
P003 Maximum Process Speed
Related
•
P005 Units
•
P007 Span
•
P700 Max Fill Rate