HydroRanger 200 – INSTRUCTION MANUAL
Page 33
m
mmmm
Oper
a
tion
Default Values
Parameter default values are indicated with an * in the parameter tables.
P000 Lock
The asterix identifies 1954 as the default value.
Parameter Reset
Returning a parameter to factory default.
1.
Display the appropriate parameter number.
2.
Display the appropriate index value (if required).
3.
Press CLEAR
.
4.
Press ENTER
.
Master Reset (P999)
Returns all parameters to original values.
Use Conditions:
•
before initial system installation
•
following a software upgrade
If complete reprogramming is required, use Simatic PDM to store and retrieve parame-
ters.
When the dual point option is enabled, P999 is indexed by transducer. Use index 00 to
reset the entire HydroRanger 200.
Display Readout
The following readouts are shown when the HydroRanger 200 cannot display a number.
Primary Index
Global
Value
1954
*
OFF: programming permitted
-1
Simulation Controls (relays energize based on
simulated level)
other
ON: Lock activated and programming not permitted
via the handheld programmer
Display
Definition
Parameter has not been set
All values not same when viewing index
0
Value too large for four-digit display