Page 214
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Pa
ra
m
e
te
rs
P845 Long Shot Width
Adjust the width (in ms) of the long shot transmit pulse.
This feature is automatically altered when Transducer (P004) is altered.
P850 Short Shot Bias
Use this feature to slant the echo evaluation in favour of the short shot echo when both
short and long shots are evaluated (see Shot Mode, P803).
P851 Short Shot Floor
Enter the minimum echo strength (in dB above 1 uV) derived from a short shot to be
considered for evaluation.
Primary Index
Single Point Model
Dual Point Model
Global
Transducer
Values
Range: 0.000 to 5.000
Altered By
•
P004 Transducer
Related
•
P841 Long Shot Number
•
P844 Short Shot Width
•
P843 Long Shot Frequency
Primary Index
Single Point Model
Dual Point Model
Global
Transducer
Values
Range: 0 to 100
Preset: 20
Related
•
P803 Shot / Pulse Mode
•
P840 Short Shot Number
•
P842 Short Shot Frequency
•
P844 Short Shot Width
•
P851 Short Shot Floor
•
P852 Short Shot Range
Primary Index
Single Point Model
Dual Point Model
Global
Transducer
Values
Range: 30 to 100
Preset: 50
Related
•
P840 Short Shot Number
•
P842 Short Shot Frequency
•
P844 Short Shot Width
•
P850 Short Shot Bias
•
P852 Short Shot Range