7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 59
mm
mmm
Pu
m
p
C
o
n
tr
o
l
Other Pump Control Algorithms
Set Relays to ALTERNATE DUTY BACKUP [6 relay model]
Set the Relay ON Setpoints [6 relay model]
Set the Relay OFF Setpoints [6 relay model]
Set Relays to FIXED DUTY ASSIST
Set the Relay ON Setpoints
Set the Relay OFF Setpoints
Parameter
Index
Value
Description
P111
1
53
Sets the pump relays (index 1, 2, and 3) to
ALTERNATE DUTY BACKUP.
P111
2
53
P111
3
53
Parameter
Index
Value
Description
P112
1
0.4m
Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
Subsequent cycles rotate the setpoints
among the pumps.
P112
2
0.3m
P112
3
0.2m
Parameter
Index
Value
Description
P113
0
1.3m
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
Parameter
Index
Value
Description
P111
1
50
Sets the pump relays (index 1, 2, and 3) to
FIXED DUTY ASSIST. Multiple pumps can run
simultaneously.
P111
2
50
P111
3
50
Parameter
Index
Value
Description
P112
1
0.4m
Sets the three setpoints for the pump relays.
The setpoints remain attached to the pump
relays.
P112
2
0.3m
P112
3
0.2m
Parameter
Index
Value
Description
P113
0
1.3m
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.