Page 32
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmmmm
Ope
rat
ion
Security
The Lock parameter P000 secures the HydroRanger 200 against parameter changes via
the handheld programmer. The unit can still be put into PROGRAM mode when locked,
and parameter values can be viewed, but no parameter values can be changed.
When P000 is set to 1954, programming is enabled. To disable programming, enter
another value.
P000 (1954) is a fixed value password. Therefore, you should use other means to secure
the HydroRanger 200 if security is a concern.
Simulation
P000 Lock also controls how simulations affect control relays. By default, control relays
are unaffected by simulation levels. But if P000 is set to –
1
, they react to the simulated
level. See
Parameters P925–P927
on page 220 for running a simulation.
Using Units or Percent (%)
Many parameters can be viewed either in measurement units (P005) or as a percentage.
View the parameter and then press MODE
to toggle between units and percentage.
The LCD shows the selected measurement type, either units (m, ft) or percentage (%).
6 relay model only:
Percentage is also available when showing flow and volume with 100%, based on the
parameter that defines the maximum.
Parameters Types
View Only Parameters
Parameter values indicating status only. They cannot be altered.
Global Values
Parameter values common to all inputs and outputs on the HydroRanger 200.
When a global parameter is accessed, the index display automatically disappears. When
a non-global parameter is accessed, the index display reappears showing the last index
number.
Measurement
Maximum
Volume
P051
Flow
P604
Содержание HydroRanger 200
Страница 1: ...Instruction Manual July 2009 200 hydroranger ...
Страница 232: ...Page 222 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Parameters Notes ...
Страница 264: ...Page 254 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Appendix H Software Rev Notes ...
Страница 278: ...Notes ...
Страница 279: ......