HydroRanger 200 – INSTRUCTION MANUAL
Page 125
mmm
mm
Pa
ra
m
e
te
rs
P052 Tank Dimension A [6 relay model]
Dimension A as used in P050 Tank Shape.
Enter one of the following:
•
height of the tank bottom if P050 = 2,3,4, or 5
OR
•
length of one end section of the tank if P050 = 7, in Units (P005)
P053 Tank Dimension L [6 relay model]
Dimension L as used in P050 Tank Shape.
Enter the following:
•
tank length (excluding both end sections) if P050 = 7
P054 Level Breakpoints (Universal Volume Calculation)
[6 relay model]
When the tank shape is too complex for any of the preconfigured shapes, you can specify
the volume based on segments. See “Accessing a Secondary Index” on page 115
for
more information
.
Enter the following:
•
up to 32 level breakpoints (where volume is known) if P050 = 9 or 10
Primary Index
Level
Values
Range: 0.0 to 99.00 m (or equivalent depending on units)
Preset: 0.000
Related
•
P050 Tank Shape
Primary Index
Level
Values
Range: 0.0 to 99.00 m (or equivalent depending on units)
Preset: 0.000
Related
•
P050 Tank Shape
Primary Index
Level
Secondary Index
Breakpoint
Values
Range: 0.0 to 99.00 m or Max. volume (P051) (or equivalent depending on
units)
Related
•
P055 Volume Breakpoints