7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 43
mm
mmm
Relay
s
[1 OR 3 relay model]: Functions affected by setpoint are configured by parameters that
determine the application requirements such as timing.
P111 Relay Control function
(see
page 133) sets the functions requirements.
[6 relay model]: Functions affected by setpoint are configured by parameters that
determine the application requirements such as timing.
P111 Relay Control function
(see
page 133) sets the function requirements. Other function parameters:
• P132–Pump Start Delay
• P133–Pump Power Resumption Delay
• P645–Relay Duration
Relay Logic is Modified
Normal operating conditions means that alarms are off and pumps are on. This can be
reversed using P118–Relay Output Logic.
Relay Failsafe
P129–Relay Failsafe
Adjusts how individual relays react to a failsafe condition. Relays can be set to:
•
OFF
Control is by P071–Failsafe Material Level
•
HOLd
Keeps the relay in the current state
•
dE
De-energizes the relay (default for pump controls)
•
En
Energizes the relay