P772 Baud Rate
The communication rate with the master device.
This specifies the rate of communication in Kbaud. Any value may be entered but only the
values shown above are supported. The baud rate should reflect the speed of the
connected hardware and protocol used.
P773 Parity
The serial port parity.
Ensure that the communications parameters are identical between the HydroRanger 200
and all connected devices. For example, many modems default to N-8-1 which is No
parity, 8 data bits, and 1 stop bit.
P774 Data Bits
The number of data bits per character.
Primary Index
Communications Port
Values
4.8
4800 baud
9.6
9600 baud
19.2
*
19,200 baud (preset for port 2)
115.2
*
115,200 baud (preset for port 1)
Primary Index
Communications Port
Values
0
*
No Parity
1
Odd Parity
2
Even Parity
Primary Index
Communications Port
Values
Range: 5 to 8
8
*
Modbus RTU
7 or 8
Modbus ASCII
7 or 8
Dolphin Plus