Set Relays to ALTERNATE DUTY ASSIST
Set the ON Setpoints
Set the OFF Setpoints
Setting a Pump Up (Reservoir) Group
Sets a group of three pumps to pump up a reservoir.
Parameter
Index
Value
Description
P111
1
52
Sets the pump relays (index 1, 2, and 3) to
ALTERNATE DUTY ASSIST.
P111
2
52
P111
3
52
Parameter
Index
Value
Description
P112
1
1.0m
Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
Subsequent cycles rotate the setpoints
among the pumps.
P112
2
1.1m
P112
3
1.2m
Parameter
Index
Value
Description
P113
0
0.5m
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
P006
P007
Inflow
Outflow
HydroRanger 200