Periphery board (2 loops) FCI2002-A1
7
Indicators
57
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
7.3.7
X1 supply
Pin
Designation
Description
1
#BATT
Message input from the power supply: Battery fault
2
#CONV
Message input from the power supply: Converter fault
3
#MAINS
Message input from the power supply: Mains failure
4
COMMON
Ground
5
3SRC+
Supply input for third supply source (+) [FR]
6
3SRC–
Supply input for third supply source (–) [FR]
7
VSYS+
Supply input from the power supply (+)
8
VSYS+
Supply input from the power supply (+)
9
VSYS–
Supply input from the power supply (–)
10
VSYS–
Supply input from the power supply (–)
Admissible cable cross-section: 0.2…2.5 mm²
3SRC
-
2
1
4
3
X1
6
5
3SRC+
COMMON
#MAINS
#CONV
#BATT
8
7
10
9
VSYS
-
VSYS+
VSYS+
VSYS
-
7.4
Indicators
Indications of supply and system
LED
Color
Function
Condition Meaning
H1
Red
Power Down Ready
Off
Normal operation
On
Control panel may be disconnected from the
mains.
H401
Yellow
Supply output 1 (F401)
Off
Fuse ok
On
Fuse damaged
H402
Yellow
Supply output 2 (F402)
Off
Fuse ok
On
Fuse damaged
H501
Yellow
Monitored alarm output (F501)
Off
Fuse ok
On
Fuse damaged
H601
Yellow
Monitored fault output (F601)
Off
Fuse ok
On
Fuse damaged