8
Periphery board (4 loops) FCI2004-A1
Indicators
72
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
LED
Color
Function
Condition
STATUS
DIRECTION
H115
Yellow
IO_6
Off
High input (default)
INPUT (default)
On
Low input
OUTPUT
H100
Yellow
IO_7
Off
High input (default)
INPUT (default)
On
Low input
OUTPUT
H101
Yellow
IO_8
Off
High input (default)
INPUT (default)
On
Low input
OUTPUT
H117
Yellow
IO_9
Off
High input (default)
INPUT (default)
On
Low input
OUTPUT
H118
Yellow
IO_10
Off
High input (default)
INPUT (default)
On
Low input
OUTPUT
H119
Yellow
IO_11
Off
High input (default)
INPUT (default)
On
Low input
OUTPUT
H120
Yellow
IO_12
Off
High input (default)
INPUT (default)
On
Low input
OUTPUT
FDnet indicators
LED
Color
Function
Condition
Meaning
H250
Yellow
FDnet Loops 1 and 2
(module 2)
Off
Passive (normal operation)
1 x flashing
(every 2 s)
Failsafe active (communication to PMI
interrupted)
2 x quickly flashing
(every 2 s)
Failsafe local alarm
1 x flashing
(every 1 s)
Failsafe indication (local alarm)
1 x flashing (every 1 s)
and
2 x quickly flashing
(every 2 s)
Failsafe local alarm + indication
On
Startup problems FDnet module 2 (clock)
H850
Yellow
FDnet Loops 3 and 4
(module 3)
Off
Passive (normal operation)
1 x flashing (every 2 s)
Failsafe active (communication to PMI
interrupted)
2 x quickly flashing
(every 2 s)
Failsafe local alarm
1 x flashing
(every 1 s)
Failsafe indication (local alarm)
1 x flashing (every 1 s)
and
2 x quickly flashing
(every 2 s)
Failsafe local alarm + indication
On