31
Sounder module FCA2005-A1
Indicators
184
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
31.3.4
X1 supply input and sounder input from the periphery
board
X1 sounder module
Periphery board
2 loops
Periphery board
4 loops
Pin
Designation
Description
Pin
Designation
Pin
Designation
1
+Vsys
Supply input from the
periphery board (+)
X8-5 VSYS_01 (+)
X8-7 VSYS_01 (+)
2
Ground
Supply input from the
periphery board (-)
X8-6 GND_01 (-)
X8-8 GND_01 (-)
3
Sound In +
Sounder input from the
periphery board (+)
X6-1
X5-1
4
Sound In -
Sounder input from the
periphery board (-)
X6-2 SOUND1-
X5-2 SOUND1-
Admissible cable cross-section: 0.08…1.5 mm²
1
2
X1
Ground
Vsys
3
4
Sound In-
Sound In+
-
+
31.4
Indicators
LED
Color
Function
Condition
Meaning
H1
Green
Supply
Off
No supply (fuse may be defective)
On
Normal condition
H2
Yellow
Sounder 2 fault
Off
Normal condition (default)
On
Sounder 2 fault (open line, short-circuit)
H3
Yellow
Sounder 1 fault
Off
Normal condition (default)
On
Sounder 1 fault (open line, short-circuit)
H4
Yellow
Sounder 3 fault
Off
Normal condition (default)
On
Sounder 3 fault (open line, short-circuit)
H5
Yellow
Sounder 4 fault
Off
Normal condition (default)
On
Sounder 4 fault (open line, short-circuit)
31.5
Technical data
Supply input
Designation
'Vsys', 'Ground'
Operating voltage
DC 21…28.6 V
Quiescent current
20 mA, typical
Operating current
Max. 2 A, protected with 2AT