43
Fire brigade periphery module FCI2001-D1 [DE]
Pin assignments
244
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
Pin
Designation
Description
3
Riegelkont -
Latch contact (-)
2
H
Heating (+)
1
Heizung -
Heating (-)
Admissible cable cross-section: 0.2…1.5 mm²
5
6
X5
Entriegel -
Ent
7
8
Sabotage -
Sa
1
2
Heizung -
H
3
4
Riegelkont -
Rieg
2.2k
-
+
-
+
-
+
-
+
5
6
7
8
10
1
2
1*
2*
3*
5 W
1* Door contact
2* Drill protection
3* Key contact
When an alarm is pending, the key depot for the heating is disconnected from the
power supply for reasons of product safety. Only when the alarm is reset, is it
again connected to the power supply.
43.3.3
X4 remote transmission /release element
Pin
Designation
Description
6
+24V
Operating voltage (+24 V)
5
UE Alarm+
Remote transmission/device alarm (+)
4
UE Alarm-
Remote transmission/device alarm (-)
3
UE Rueckm
Remote transmission /device acknowledgement (+)
2
FSE+
Release element with monitored remote switching output or
separately monitored key switch
1
FSE-
Admissible cable cross-section: 0.2…1.5 mm²