Fire brigade periphery module FCI2001-D1 [DE]
43
Pin assignments
245
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
3
4
X4
UE Rueckm
UE Alarm -
5
6
UE Alarm +
1
2
FSE -
200 ... 2k
3.3k
680
+
-
+
-
+
ST
ST Fault contact of the transmission device
43.3.4
X2 fire department operating panel / X3 fire department
operating panel
X2 fire department operating panel
Pin
Designation
Description
8
+24V
Operating voltage (+24 V)
7
0 V
Operating voltage (-)
6
UE ausgel
Transmission transmission triggered
5
LA ausgel
Extinguishing system triggered
4
Bf St ab
Fire controls off
3
Ak Sign ab
Acoustic signals off
2
BMZ rueckst
Reset fire control panel
1
UE ab
Remote transmission off
Admissible cable cross-section: 0.2…1.5 mm²
X3 fire department operating panel
PIN
Designation
Description
8
Bf St ab
Fire controls off
7
Ak Sign ab
Acoustic signals off
6
BMZ rueckst
Reset fire control panel
5
UE ab
Remote transmission off
4
UE pruefen
Check remote transmission
3
Reserve
Reserve output
2
Reserve
Reserve input
1
Not used
Admissible cable cross-section: 0.2…1.5 mm²