Operating unit with PMI & mainboard FCM2027
11
Description
83
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
11
Operating unit with PMI & mainboard
FCM2027
11.1
Description
The operating unit with PMI & mainboard FCM2027 includes the CPU module
(MPC8248) and the Person Machine Interface. The PMI & mainboard FCM2027 is
used in all operating units from MP-EN 4.0 onwards.
The optional operating units of the panels FC2080 and FG2020-D1 must be
equipped with the PMI & mainboard FCM2027. Panels with index ES20 or higher
come with the PMI & mainboard FCM2027 included.
The PMI & mainboard FCM2027 has the following features:
Ground fault monitoring of system supply
Integrated real time clock, maintains the time function for at least 2 days in the
event of power failure.
Shield plate
Interface to the periphery board
Slot for a networking module (SAFEDLINK) with full functionality
Slot for a networking module (SAFEDLINK) with degraded mode function
Ethernet connection for:
– maintenance PC or
– Networking via LAN, with switchable ground fault monitoring
Slots for serial options:
– RS232 module for the connection of an event printer
– RS485 module for the connection of other devices such as ESPA-4.4.4.
interface, FAT [DE], FDF [DE], UGA [FR] or remote EVAC-NL operation
– Connection module (card cage)