Communication card (FG2020-D1) FCC2008-D1
36
Indicators
207
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
36.3
Indicators
4
1
2
3
5
6
7
LED indicators of the communication card on the front side
LED
Color Function
Condition
Meaning
1
Green FCnet SDLM On
Network module (SAFEDLINK, CC) FN2010-A1 is installed
Green FCnet Run
Off
Network module (SAFEDLINK, CC) FN2010-A1 is defective
On
Normal condition (displays for status of lines 1 and 2 are off)
Flashes
Normal condition for degraded mode module (displays for status of lines 1
and 2 are off)
Yellow FCnet
Line 1
Off
Normal condition (communication on line 1 is OK)
On
Fault on line 1 (no communication on line 1)
Yellow FCnet
Line 2
Off
Normal condition (communication on line 2 is OK)
On
Fault on line 2 (no communication on line 2)
2 ... 6 Yellow Ethernet
Port 5
to
port 1
On
100 Mbit link connection
Off
10 Mbit link connection
Green
Lit up
Line connection active, no data transfer
Flashes
Data transfer on link
7
Green OK
Fail
On
Normal operation
Yellow
On
Malfunction