I/O card (RT) FCI2007-A1
30
Technical data
179
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
Monitored output
RT alarm/horn
Designation
'Fire Output 1+'; 'Fire Output 1-'
'Fire Output 2+'; 'Fire Output 2-'
Design
Load or
EOL monitoring with calibration
Monitored fuse in operation
Activated in degraded mode operation (RT
alarm/horn can be switched off)
Output voltage
DC 26.4…27.6 V (DC 27.2 V -3 % +1.5 %)
Output current
Max. 2 A
Loading capacity
Max. 470 µF
Monitored for (active and inactive)
Short-circuit
Open line
Measuring range, monitoring resistor 40…6100
Range of termination resistor
(Reol) for load with diode
decoupled (EN54)
45…5500
Range of the load resistance
(Rload) with load resistor
monitoring (VdS)
45…5200
Line resistance (both cables)
Max. 200
Monitoring tolerance
Load resistance monitoring (VdS): ± 10 %
Load with diode decoupled (EN 54): ±7.1 %
transient ±2.5 %
Measurement cycle
1 s
Status monitoring
4 s
Duration of the monitoring interruption
when activation was deactivated.
30 s
Duration of calibration
25 s
Configurable inputs/outputs
1 … 2
Designation
'RT_Response/GPIO1' and 'GPIO2'
Individually configurable as
Input
Output
Configured as input:
Design
Threshold values
Digital
Not monitored
GPIO1 configurable as RT_Response possible
>18 V = off
<9 V = on
Configured as output:
Design
Open drain
Inherently short-circuit-proof
Output voltage
DC 26.4…27.6 V (DC 27.2 V -3 % +1.5 %)
Output current per output
Max. 300 mA
Mechanical data
Dimensions (L x W x H)
160 x 120 x 15 mm
Weight
119 g
Ambient conditions
Operating temperature
Min. -5 °C max. +50 °C
Storage temperature
Min. -20 max. +60
Air humidity
Max. 93 % rel. air humidity (EN 60068-2)
Standards and approvals
VdS
QA Standards
CE conformity mark
LPCP