Operating unit with PMI & mainboard FCM2004
10
Indicators
81
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
X11 Slot for connection module (card
cage) FCA2006-A1
S38 Switches for booting and operation
system options
X12 Slot for network module
(SAFEDLINK) FN2001-A1;
degraded mode module
1
The serial modules can be loaded in any way. Two identical modules for each
PMI & mainboard can also be loaded.
10.3
Indicators
LED
Color
Function
Condition
Meaning
H32
Yellow
LINK control indicator
Off
No Ethernet connection
On
Ethernet connection established
H36
Yellow
Processor status indicator
Off
Processor in normal operation
On
Processor in degraded mode; replace
component or contact hotline
H37
Red
Processor status indicator
Off
Processor in normal operation
On
Processor in degraded mode
H38
Red
Installation ready for switching off
Off
Installation in operation
On
Installation may be disconnected from the
mains
H39
Red
Processor status indicator
Off
Processor in normal operation
On
Processor in degraded mode; replace
component or contact hotline
H297
Red
Reserved
10.4
Adjustment elements
S32: Reset key
Operation
Function
Press for <2 s
Station is shut down and restarted in a controlled manner. This
procedure takes up to 5 minutes.
Press for >2 s
Station is shut down and restarted immediately. This may lead to
data loss. This procedure takes up to 5 minutes.
Press S32 + positions
S38-2 or S38-1
See below, S38
Update firmware or restore factory settings
S38: Switches for booting and operation system options
The two S38 switches have independent functions. Both switches are in the 'OFF'
position as standard.
S38-2 has an impact on booting.
The setting of S38-2 has priority over the setting of S38-1.
Position S38-2
Function
ON
Station's firmware is updated.
OFF
Station is started normally.