18
Repeater (SAFEDLINK) FN2002-A1
Indicators
114
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
18.4
Indicators
LED
Color
Function
Condition
Meaning
H1
Green
Condition of the repeater
(SAFEDLINK)
Flashes
Normal condition
Off
Repeater (SAFEDLINK) is defective
H2
Yellow
Condition of the line 2
(A2, B2)
On
Fault on connection line 2;
Repeater (SAFEDLINK) is OK
Off
Normal condition
H3
Yellow
Condition of the line 1
(A1, B1)
On
Fault on connection line 1;
Repeater (SAFEDLINK) is OK
Off
Normal condition
H4
Red
Ground fault
On
Ground fault on connection line 2;
Repeater (SAFEDLINK) is OK
Off
Normal condition
18.5
Technical data
Supply input
Voltage
DC 9…30 V
1
Operating current
Max. 45 mA
System bus
Voltage
DC 5 V
Current
Max. 100 mA
Impedance
120
Protocol
SAFEDLINK (UDP/IP)
Data rate in operation mode:
Speed
312 kbit/s
Distance
96 kbit/s
Distance between repeater and network module
Max. 1000 m
Electrical isolation between the FCnet and the
station
1 kV
Monitored for:
Short-circuit
Open line
Ground fault
Communication error
Connections
System bus:
Design
Screw terminals type Phoenix
MC1,5/x-ST-3,81
0.8 … 1.5 mm
2
(0.8 mm
2
recommended)
Operating unit
Plug-type connection
Mechanical data
Dimensions (W x H x D)
90 x 25 x 132 mm
Weight
105 g
Standards
VdS
G211003
1
The supply voltage may significantly decrease along the supply line from the
station to the repeater. To ensure the reliable operation of the repeater, the
terminal voltage must be at min. 9 V.