I/O card (programmable) FCI2008-A1
Technical data
164
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
28.6
Technical data
General
Number of freely programmable I/Os
12
Ground fault detection
Via PMI & mainboard
Supply
Operating voltage
Vsys 20…30 V
Operating current
Max. 2 A
Supply outputs 1 and 2
Designation
'VSYS_01', 'VSYS_02'; 'GND'
Voltage
DC 21…28.6 V
Current
Max. 1 A (protected with 1 AT)
Configurable
Inputs/outputs 1…12
Designation
'I/O1' … 'I/O12'
Individually configurable as
Input
Output
Configured as input:
Design
Digital
Not monitored
Threshold values
> Vsys/2 = off
< Vsys/4 = on
Configured as output:
Design
Open drain
Inherently short-circuit-proof
Excess temperature protection
Output voltage
DC 21…28.6 V
Output current per output
max. 300 mA
Output current of all outputs (total)
1.5 A
Configuration of degraded mode behavior
Open
Closed
Fixed
Alternating quickly
Alternating slowly
Activated by horn emergency alarm
Mechanical data
Dimensions (L x W x H)
160 x 120 x 15 mm
Weight
104 g
Ambient conditions
Operating temperature
Min. -5 °C max. +50 °C
Storage temperature
Min. -20 max. +60
Air humidity
Max. 93 % rel. air humidity (EN 60068-2)
Standards and approvals
VDS
QA Standards
CE conformity mark
LPCP