Line card (FDnet/C-NET) FCL2001-A1
25
Technical data
149
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
25.6
Technical data
Supply input
Voltage
DC 20…30 V (Vsys)
Current
Max. 0.8 A
Detector line
Output voltage
Max. DC 33 V
Output current (total)
Max. 0.5 A
Plug-type connection for card cage
Addressable devices
Max. 252
Connectable lines
4 loops or 8 stubs (mixed variants are possible)
Protocol
FDnet
Cable types
All types (recommended: twisted); for detailed
specifications see document 008843
Monitored for
Ground fault
Short-circuit
Open line
Line capacitance
Design
Short-circuit-proof
Overvoltage protection (on card cage)
Mechanical data
Dimensions (L x W x H)
160 x 120 x 15 mm
Weight
119 g
Ambient conditions
Operating temperature
Min. -5 °C max. +70 °C
Storage temperature
Air humidity
Min. -20 max. +60
Max. 93 % rel. air humidity (EN 60068-2)
Standards and approvals
VDS
QA Standards
CE conformity mark
LPCP