21
Safety module (firewall) FN2009-A1
Technical data
134
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
21.6
Technical data
Supply input
Voltage inputs
DC 18…32 V each, decoupled
Operating current
Max. 250 mA
Ethernet
Bushes
2 x RJ45, 10/100 Mbit/s, automatic sensing
Red port = external network
Green port = internal network
Length of line
Max. 100 m via FC TP standard cable
Connections
Supply inputs
4-pin terminal
Detector contact
Connection
2-pin terminal
Load
Max. 100 mA can be loaded
Monitored for
Internal error
Error in voltage supply
Software outline quantities
Firewall function
max. 256 standard rates
VPN function
max. 64 channels (IPsec tunnels or not encrypted)
Mechanical data
Dimensions (W x H x D)
60 x 125 x 124 mm
Weight
780 g
Ambient data
Storage temperature
-40…+80 °C
Operating temperature
0…+60 °C
Rel. humidity in operation
95 %, non-condensing
Protection category
IP30
FN2009-A1 is class A equipment and may cause radio interference in residential
areas. If interference does occur, observe the modifications to wiring in document
008851, Installation.