I/O card (RT) FCI2007-A1
Technical data
178
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
30.6
Technical data
General
Ground fault detection
For FC2080 and FG2020 via communication
card
For FC2030 and FG2060 via PMI & mainboard
Supply
Operating voltage
Vsys 20…30 V
Quiescent operating current
70 mA with Vsys 24 V
Max. operating current (at max. load) 5.6 A with Vsys 20 V
4.7 A with Vsys 24 V
Maximum load on the outputs Total current from the supply output,
monitored and configurable outputs
Max. 4 A
Supply output
Designation
'0 V', '27V2'
Voltage
DC 26.4…27.6 V (DC 27.2 V -3 % +1.5 %)
Current
Max. 2 A (electronically fused)
Changeover contacts
RT alarm
Designation
’AL_NO’; ’AL_COM’; ’AL_NC’
Design
Relay output
Break or make contact
Activated in degraded mode
Switching voltage
Max. DC 36 V
Switching current
Max. 400 mA
Changeover contacts
RT fault
Designation
'FAU_NO'; 'FAU_COM'; 'FAU_NC'
Design
Relay output
Break or make contact
Activated in degraded mode
Switching voltage
Max. DC 36 V
Switching current
Max. 400 mA
Monitored output
Fault
Designation
'R'; 'RT_Fault-'
Design
Load monitoring with calibration
Activated in degraded mode operation (fault
can be switched off)
Output voltage
DC 26.4…27.6 V (DC 27.2 V -3 % +1.5 %)
Output current
Max. 0.3 A
Loading capacity
Max. 470 µF
Monitored for (active and inactive)
Short-circuit
Open line
Measuring range, monitoring resistor 120…6000
Range of load resistor (Rload)
150…4300
Line resistance (both cables)
Max. 200
Monitoring tolerance
± 25 %
Measurement cycle
1 s
Status monitoring
4 s
Duration of monitoring interruption
after switchover
30 s
Duration of calibration
20 s