Fire terminal board FTI2001-A1
6
Indicators
49
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
X7, supply input 1
Pin
Designation
Description
4
VSYS - 1
Ground
3
VSYS - 1
Ground
2
VSYS + 1
System supply DC 21…28.6 V (+)
1
VSYS + 1
System supply DC 21…28.6 V (+)
Admissible cable cross-section: 0.2…2.5 mm²
4
3
X7
VSYS -1
VSYS -1
2
1
VSYS +1
VSYS +1
-
+
-
+
6.4
Indicators
LED
Color Function
Condition Meaning
H101 … H103 Red
Power Down Ready
Off
Normal operation
On
Control panel may be disconnected from the
mains
H201
Yellow Supply output 1
Off
Fuse ok
On
Fuse damaged
H202
Yellow Supply output 2
Off
Fuse ok
On
Fuse damaged
H203
Yellow Monitoring of the voltage at the
supply input 2 'VSYS2'
1
Off
Supply available
On
No supply and monitoring is switched on
(S1-1 = ON)
H204
Yellow Monitoring of the voltage at the
supply input 1 'VSYS1'
1
Off
Supply available
On
No supply and monitoring is switched on
(S1-2 = ON)
H207
Yellow Monitoring power supply
'CONVERT_DEF_IN'
On
Fault in the power supply unit
Off
Normal condition
H206
Yellow Monitoring mains voltage
'MAINS_FAIL_IN'
On
No mains voltage
Off
Normal condition
H205
Green Monitoring batteries 'BATT_DEF_IN' On
Battery fault
Off
Normal condition
1
For a correct indication the switch S1 must be in the corresponding position!