EVAC-NL operating unit FTO2007-N1
Adjustment elements
254
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
44.5
Adjustment elements
The EVAC-NL indicator is configured with the switch S20.
Setting for one or the first EVAC-NL
Switch S20
Meaning
1
2
3
4
5
6
S0 S1 S2 Master Syn (Empty)
ON
OFF
Device address 1
1
ON
ON
OFF
Device address 2
ON
ON
OFF
Device address 3
ON ON
ON
OFF
Device address 4
ON ON
OFF
Device address 5
X
X
X
ON
ON
Mimic display outputs are actuated and
polled (LED, keys and key switch)
Blank fields = Switch in 'OFF' position
X = Switch position has no impact
1
If working with a single EVAC-NL indicator (10 zones) and if working with the first
EVAC-NL indicator, S20/4 (Master) must always be set to ON. If used in the EVAC-
NL mimic display driver, the S20/5 (Syn) switch must also be ON.
Each address can be assigned only once per station.
The factory setting is always made for the application in question.
Setting for the second and/or any subsequent EVAC-NL indicator
Switch S20
Meaning
1
2
3
4
5
6
S0 S1 S2 Master Syn (Empty
)
OFF
OFF
Device address 1
ON
OFF
OFF
Device address 2
1
ON
OFF
OFF
Device address 3
ON ON
OFF
OFF
Device address 4
ON OFF
OFF
Device address 5
X
X
X
OFF
ON
Mimic display outputs are actuated and
polled (LED, keys and key switch)
Blank fields = Switch in 'OFF' position
X = Switch position has no impact
1
2 EVAC-NL indicators must not be operated on the same address (per station).
On the second or any subsequent indicator, the address must always be set 1
higher (slave). If used in the EVAC-NL mimic display driver, the S20/5 (Syn) switch
must also be ON.